Station Smoke Reservoir Screening

Underground stations, fire and life safety

See how fast the smoke layer descends at each station, check it against the NFPA 130 evacuation times, and pick the stations that go forward to CFD.

4 minPlatform evacuation timeNFPA 130, 5.3.3
6 minEvacuation to a point of safetyNFPA 130, 5.3.3
Preliminary analysis only

A simplified zone-model screen for comparing stations and prioritising them for study. It does not replace CFD analysis, an egress calculation or a tenability assessment, and must not be used to demonstrate compliance or for design.

1Stations

Enter a station and watch its reservoir fill. Add the next station when you are ready.

Heights are to scale, with the figures 1.75 m tall. Widths are schematic. The hatched block is the share of the reservoir taken by services.

Clear of smokeLayer at or below the critical heightLayer at or below head height, 1.75 m

2Scenario

Assumptions applied to every station. Change one and all results update.

Design fire

Tenability and time limits

NFPA 130 platform evacuation240 s
NFPA 130 point of safety360 s

Smoke extract

Off by default, which gives the pure filling time.

Downstand and services

Selection for CFD

3Compare and select

Vulnerability ranking

RankStationEffective reservoir (m³)Spill under downstand (s)Critical height (s)Margin on 4 min (s)Margin on 6 min (s)Lowest layer (m)NFPA 130 time check

Shaded rows are selected for CFD. Click a row to open that station in step 1. Stations where the layer never reaches the critical height are ranked last, by lowest layer height.

Smoke layer height over time

Each station has its own line style and carries its rank number. Orange lines are selected for CFD. Point at a station in the key or the ranking to isolate its curve.

?Help

How to operate the tool. The full user guide opens as a separate page.

  1. In step 1, type the station name and its five values. The section and results update as you type.
  2. Press Play, or drag the time slider, to watch the reservoir fill. The figures turn orange at the critical height and red when smoke reaches head height.
  3. Press + Add station for the next station, or paste a whole list from Excel.
  4. In step 2, set the fire, extract, downstand and selection assumptions that apply to every station.
  5. In step 3, read the ranking and chart, then copy the ranking as CSV. Shaded rows are the stations selected for CFD.
Open the full user guide

Keep help.html in the same folder as this file.

Method, time limits and limits of use

Time limits. NFPA 130 (stations, means of egress, Section 5.3.3) requires enough egress capacity to evacuate the platform occupant load from the platform in 4 minutes or less, and evacuation from the most remote point on the platform to a point of safety in 6 minutes or less. This tool uses those two times, 240 s and 360 s, as the limits the smoke layer is checked against. Confirm the clause numbers and values against the edition adopted on the project.

Calculation. Each station is one smoke zone bounded by its downstands. The fire grows as Q = α t² up to the peak. The plume entrains air up to the layer base using the axisymmetric plume relation in NFPA 92, with z the clear height from floor to layer base and Qc the convective heat release in kW:

Layer temperature is Ts = T0 + (1 − loss) Qc / (m cp), and the volume added each second is m Ts / 353. Extract, when included, removes its volume rate multiplied by the extraction efficiency after the start delay. The efficiency is the share of the extracted flow that is smoke from the layer, the rest being clear air drawn from below. Inside the downstand depth the plan area is reduced by the services blockage. Where the blockage is not known, it can be assigned from a normal distribution truncated to the chosen range (20 to 50% by default), centred on the midpoint with the range taken as six standard deviations. Below the downstand the full plan area applies, which assumes the smoke stays within the same footprint.

Not modelled. Smoke spill to adjacent zones and floors, ceiling jet transport time, tunnel and piston air movement, inlet air effects, non-uniform layers, visibility and toxicity. The figure colours are indicators only: orange when the layer base is at or below the critical height, red when it is at or below a 1.75 m head height. The evacuation times are the NFPA 130 limits, not a calculated egress time for each station.